Seam Probing
December 5, 2019

Seam probing is an important final step in the hot air welding process because it is a good indicator to determine if proper fusion has occurred between the membrane layers. Whether the membrane is TPO or PVC, both products need to be probed – but with slightly different techniques.

Probing must be done once hot air welds have thoroughly cooled (at least 20 minutes). Premature probing can damage warm seams. Hot air welded seams must be probed throughout the day to check seam quality and to make proper adjustments to hot air welding equipment. The repair of deficiencies must be done routinely throughout the day, but no later than the end of each workday.

A blunt or dull cotter pin puller is an acceptable tool to perform the probing task. Versico offers a custom-designed Seam Probe that incorporates an ergonomic, threaded handle with a heat-treated, plated steel tip. With continued use these tools will wear down, creating a tip that is too sharp for probing. Blunting the tip is necessary when this occurs.

When a substantial amount of probing is necessary, an extension pole can be threaded into the handle of the Versico probe. This allows the operator to stand up while probing long runs of field seams.

Getting started
Draw your probing tool tip along the edge of the heat welded seam. Apply firm pressure to probe the seam junction, but not into the bottom membrane sheet. The tool will not penetrate into the lap area of a properly welded seam. If the seam probing tool penetrates into the welded overlap area, use a water-soluble marker to mark the beginning and the end of voids or wrinkles in the seam edge.

Repair seam deficiencies as soon as possible using the hand held welder. Versico recommends that repairs be made the same day deficiencies are discovered. Probe repaired seams after they have cooled completely. If the repair is acceptable, wipe off the water-soluble marker lines; if not acceptable, repair the seam using standard heat welded overlay procedures. Another reason all laps must be probed each day soon after they have cooled is to verify the welder set-up is effective. Particular attention must be given to all membrane intersections and heat welded seams at insulation joints. In addition, there should be periodic checks (including at the start of each day) to verify good peel strength.

Considerations when probing TPO systems
1.) TPO does not "flow" like PVC. If you observe an area in which you see "flow" of the bottom ply, scorched areas of detail/flashing membrane, or scorched field membrane welds, these areas should be probed. If these areas are overheated to the point of membrane damage, an overlay repair will be required even if the weld probes successfully.

2.) A properly heated field membrane weld will typically have a visual "sheen" approximately 1/2" wide on the bottom sheet at the weld overlap. When walking seams, look for the sheen. If it is not present, probe to ensure weld quality.

 3.) TPO seams require a minimum 1.5" weld. Welds less than 1.5" must be overlaid as stated in Versico’s specifications and details, even if probing does not produce deficiencies.

Considerations when probing PVC systems
1.) Welds on PVC systems should produce "bleed out". Bleed out refers to the flow of the bottom ply (of the top sheet) outside of the weld. If you do not see bleed out at seam areas, this increases the probability the seam did not receive enough heat when it was welded. Be sure to probe these areas to ensure weld quality.

2.) PVC is a “softer” and more flexible membrane than TPO. As such, a different probe should be used than the one used on TPO roofing systems. The PVC probe should have a blunt/dull tip, or utilize a "hook" screwdriver with a flat head.

 3.) PVC seams require a minimum 1.5" weld. If you observe welds which are less than 1.5", these should be overlaid following specifications and details, even if probing does not produce deficiencies.

Remember, application of Cut Edge Sealant should not begin until all probing is completed.

Please contact Jim Gage with questions.


    Jim Gage
    Senior Technical Specialist
    Product Marketing
    james.gage@carlisleccm.com
February 20, 2020
Code-Required Minimum R-Values

Over the past 10 years, there has been a shift in minimum required R-values. The 2015 International Energy Conservation Code (IECC) is the driving force behind this movement. More than 20 states have adopted the 2015 IECC, or a portion of its provisions, as their statewide energy code. See the chart below for minimum R-values per climate zone. Since 2009, the roofing industry has seen an R-10 increase in the majority of the states. The total minimum insulation thickness has increased from 3.5" (R-20) to 5.2" (R-30) in parts of over 40 states. The map below can help you identify climate zones within your state. Climate zones 4 through 8 have experienced an R-10 increase. Additional resources are provided below to help you determine the applicable energy code and its associated minimum R-value requirements in a given state or local jurisdiction.    1. Minimum Insulation R-value Requirements: Non-Residential, Above Roof Deck    2. The Building Codes Assistance Project For more information on R-value requirements, please contact Brandon Reynolds at brandon.reynolds@carlisleccm.com

Read This Post
February 6, 2020
Polyiso Storage, Handling, and Application Guidelines

It is well known that moisture is detrimental to roof system performance. Wet insulation can lead to several issues including mold, reduced membrane adhesion, and ultimately roof system failure during wind events. Because wet polyiso must be removed and replaced, watertight tie-ins are essential every night. But let's take a step backwards and look at overall polyiso storage before and during installation. An appropriate understanding of storage, handling, and application will result in a properly constructed roof system. Material delivery should be carefully coordinated with the roof installation schedule to minimize outdoor storage. However, short-term outdoor storage can be necessary at times. When storing polyiso outdoors, bundles should not be stored directly on the ground. If possible, they should be stored over a finished surface rather than dirt or grass. Bundles should be covered with a waterproof cover and secured to prevent wind displacement. Exercise care when handling polyiso to prevent breaking or crushing the edges and surfaces. Polyiso should always be installed on dry roof decks and in dry conditions. Apply only as much polyiso as can be covered by completed roofing the same day. Roof surface protection (plywood) should be used in areas where storage and staging are planned to reduce direct, excessive traffic. Tips: Place bundles on pallets or included feet over a finished surface such as gravel, pavement, or concrete. Remove polyiso bundles from trucks with proper equipment. Do not push bundles off the edge of a truck or "roll" a pallet across the roof deck. Follow Versico's requirements regarding product application to ensure adequate performance of the roofing system. For more information, please contact your sales representative.

Read This Post
January 23, 2020
CAV-GRIP 3V in Cold Weather: Best Practices

As mother nature's cold hands grip much of the continent, many roofing contractors are forced close up shop until winter surrenders to spring. For many contractors, the onset of cold weather means delayed progress, but that mentality is changing. Versico's focus on innovation has resulted in new products that make cold weather installations more manageable. One product leading the pack is CAV-GRIP® 3V Low-VOC Adhesive, which can be installed in temperatures as low as 25°F (-4°C)! Like other adhesives, there are guidelines to follow when using CAV-GRIP 3V in cold weather. Here is some advice to live by: STORAGE: Whether at a distributor's shop or on the jobsite, CAV-GRIP 3V should ALWAYS be stored in protected, heated spaces with the temperature maintained above 70°F (21°C). Adhesive can thicken or gel when exposed to colder temperatures for an extended period. When reheating with a heated blanket or hot box, it can take hours to thoroughly heat the contents and re-liquify. It is recommended to reheat for 12-24 hours prior to use. If the spray gun is spitting, sputtering, or clogging, it is a good indication you've got cold material. GUARD AGAINST HEAT SINKS: A "heat sink" is a material or surface that absorbs heat from surrounding objects. Place cylinders on insulation to avoid direct contact with a cold steel or concrete decks. These surfaces will act as a heat sink, rapidly cooling the cylinders. HOT BOXES AND HEAT BLANKETS: Shop-fabricated or manufactured hot boxes and heated blankets are required to keep CAV-GRIP 3V above 70°F (21°C) when working in colder temperatures. Do not use band heaters due to risks associated with overheating a pressurized cylinder. Devising a way to insulate and heat the hoses also aids in keeping the adhesive warm and spraying properly. Removing cylinders from the cardboard box will aid in heat transfer. ROTATION: It's a good idea to preheat cylinders to 90°F (32°C) as a safety factor against wind chill. Rotate cold tanks into a hot box and replace with heated cylinders. SHAKE CYLINDERS TO AGITATE CONTENTS: Shaking cylinders is a good way to avoid settling of contents and to maintain spray pressure. SPRAYING ISSUES OR GUN CLOGGING: If the spray tip begins to spit, sputter, or clog entirely, there are two main culprits: 1. COLD MATERIAL - Clean the gun and hose from the problem cylinder with Low-VOC UN-TACK prior to attaching to a new, warm cylinder after it has been shaken. 2. CLOGGED SPRAY TIP - If spraying stops, remove the brass spray tip and spray the adhesive into a garbage bag. If the adhesive flows through the wand in a straight stream with no hesitation, then the tank is still functional (assuming it's warm). Simply clean or replace the brass tip and begin spraying again. For more information, please contact your regional manager.     Ryan Ferguson     EPDM Product Specialist     Product Marketing     ryan.ferguson@carlisleccm.com

Read This Post
X
Email to your Colleagues >
Separate multiple emails with a comma or semicolon.
Copy Me


Please log in to share this item by email.
Add to a Collection >
Please log in to share this item to your collections.
Private
Private Collection (Change)

Loading...
Invite user by email:
User Invited. Invite another
User Invite Failed, try again.
X
Visibility Options
Public Collection
Anyone with a link can view. No sign-in required.
Private Collection
Only people explictly granted permission can access. Sign-in required.
X

You are now working in your copied collection
Okay